Permit: T03EL01565
Permit Details
Status:
Final
Type:
SINGLE FAMILY OTHER
Address:
1702 N GREASEWOOD RD
Address NEW:
1702 N GREASEWOOD RD
Apply Date:
08/07/2003
Applicant:
SEAN RICH
Description:
UPGRADE:ELECTRIC 100AMP TO 200AMP
Contractors:
- HASKINS ELECTRIC INC ,
- U S HOME OF ARIZONA *P *C
Permit Reviews
Permit Number - T03EL01565
Permit Status: Final
Permit Description: UPGRADE:ELECTRIC 100AMP TO 200AMP
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 08/07/2003 | ELECTRICAL | 08/07/2003 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T03EL01565
Permit Status: Final
Permit Description: UPGRADE:ELECTRIC 100AMP TO 200AMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/07/2003 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T03EL01565
Permit Description: UPGRADE:ELECTRIC 100AMP TO 200AMP
Total Completed Inspections - 6
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/15/2003 | ELECTRIC - CABLE DROP | MCAPISTR | Approved | SENT TO TEP ON 08/18AM CORRETIONS REQUIRED 1. PERMANENT ADDRESS LABEL UNDER METER. 2. GAS PIPE BOND. MAY BE FONE BY JUMPING COLD WATER PIPE TO GAS PIPE AT WTR HTR. 3. LABEL CIRCUITS. 4. RECALL WHEN READY. |
| 08/15/2003 | ELECTRIC - INTERMEDIATE | MCAPISTR | Approved | IVRS - Inspection 0000* |
| 08/15/2003 | ELECTRIC - UNDERGROUND | MCAPISTR | Approved | IVRS - Inspection 0000* |
| 08/18/2003 | ELECTRIC - FINAL | MCAPISTR | Approved | IVRS - Inspection 0000*SENT TO TEP ON 08/19AM THE ADDRESS MUST BE APPLIED WITH METALLIC NUMBERS OR METALLIC EMBOSSED "DYMO" LABEL. PEN,PENCIL,OR MAGIC MARKER ARE NOT ALLOWED. |
| 08/18/2003 | ELECTRIC - SERVICE UPGRADE | MCAPISTR | Approved | IVRS - Inspection 0000* |
| 08/19/2003 | PERMIT FINALED | MCAPISTR | Approved |