Permit: T03EL01108
Permit Details
Apply Date:
06/06/2003
Applicant:
KING STEVE
Description:
RECONNECT:ELECTRIC GUARD SHACK
Outstanding Activity Conditions
Permit Number - T03EL01108
Permit Status: Expired
Permit Description: RECONNECT:ELECTRIC GUARD SHACK
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 06/06/2003 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T03EL01108
Permite Description: RECONNECT:ELECTRIC GUARD SHACK
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/09/2003 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0245*/ 1) PROVIDE ONE-LINE DIAGRAM FOR 3 DISCONNECTS AT SERVICE, LOAD CALC'S, BY ELECTRIC ENGINEER, LABEL DISCONNECTS AS TO LOAD SERVED 2) LOAD CENTER IN GUARD SHACK STRIPPED OF BREAKERS, LIGHT FIXTURES NOT COMPLETE, EXPOSED WIRING, DEVICES AND OR PLATES MISSING THRU-OUT BLDG. NEED ACCESS INTO BOARDED UP SECTION. ALL REPAIR WORK TO BE DONE BY 2/11 LICENSED CONTR. LEAVE NAME, PHONE NUMBER PLEASE. RECALL WHEN DONE |