Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
C of o
Type:
COMMERCIAL ALTERATION
Apply Date:
03/14/2003
Applicant:
PHILL MACKEY
Description:
TI:RETAIL
Contractors:
  • CORONA SIERRA INC ,

Permit Reviews

Permit Number - T03CM01300
Permit Status: C of o
Permit Description: TI:RETAIL
Start Date Submittal Complete Date Status  
03/14/2003 PLANS OK TO SUBMIT - COMM 03/14/2003 COMPLETED Review Details
03/14/2003 3RD PARTY REVIEW-COMMERCIAL TI 03/21/2003 COMPLETED Review Details
03/21/2003 REVISION 04/02/2003 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T03CM01300
Permit Status: C of o
Permit Description: TI:RETAIL
Total Outstanding Activity Conditions - 1
Date Name
03/14/2003 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T03CM01300
Permit Description: TI:RETAIL
Total Completed Inspections - 16
Date Description Inspector Results Comments
04/18/2003 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection 0000*N/H DWV INSTALLED PER PLAN. COPPER OK
POINTS OF CONNECTION OK
OK TO COVER.
04/18/2003 ELECTRIC - INTERMEDIATE RMAJUTA Approved IVRS - Inspection 0000*
1.) 30A 2P CIR WITH #10'S NEAR HAND SINK NOT IN
2.) DD 16,18 30 A CIR NOT IN FOR COOLER.
3.) NORTH WALL PLAN SHOWS 4 RECEPTACLE ONLY. 2 INSTALLED PLASTER RINGS ONLY SINGLE

NOTE
1.) WATER HEATER CIRCUIT CHANGED TO 120V
2.) COOLER CHANGED TO 120V
3.) PLASTER RINGS FOR 4 RECEPTACLES CHANGED OUT.
4.) WILL NEED TO SEE HOW CIRCUITLY RUN IN CEILING.
04/23/2003 ELECTRIC - FINAL MCAPISTR Approved IVRS - Inspection 0000*
04/23/2003 ELECTRIC - ABOVE CEILING MCAPISTR Approved
04/23/2003 FRAMING HLEYVA Approved
04/24/2003 PLUMBING - FINAL RMYERS Approved CORRECTIONS MADE OK
2.) OK FOR C OF O PENDING ANY OTHER INSPECTION.
04/24/2003 PLUMBING - FINAL RMYERS Approved IVRS - Inspection 0999*1.) NOTICE THAT SINKS ARE PLUGGED.
2.) NOTICE THAT THERE ARE SEVERAL LEAKS WET SPOTS IN CABINET.
3.) T & P RELIEF DRAIN TO BE FULL SIZE.
4.) BAR SINK NOT SECURED.
5.) SINKS NOT CAULKED.
04/24/2003 PLUMBING - ROUGH, SOIL RMYERS Approved
04/24/2003 BUILDING - FINAL LHANLY Approved IVRS - Inspection 0000*STEEL CURTAIN BEAM MODIFIED TO HANG FROM EXISTING SOFFITS. STRUCTURAL OK.
04/24/2003 BUILDING ABOVE CEILING LHANLY Approved
05/01/2003 RIGHT OF WAY - FINAL MOTERO Approved
05/01/2003 ENGINEERING - FINAL JBRUCKME Approved
05/01/2003 FIRE - FINAL JEGAN Approved IVRS - Inspection 0000*
05/01/2003 FIRE SPKLR - FINAL JEGAN Approved IVRS - Inspection 0000*
05/02/2003 PERMIT FINALED JYBARRA Approved
05/02/2003 SIGN - FINAL JYBARRA Approved

Documents

File Name Document Type  
None CERT OF OCC VIEW