Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T02ME00379
Permit Details
Apply Date:
06/20/2002
Applicant:
ORACLE CONTROL SYSTEMS INC ,
Description:
INSTALL: A/C (APA)
Contractors:
- ORACLE CONTROL SYSTEMS INC ,
Outstanding Activity Conditions
Permit Number - T02ME00379
Permit Status: Closed
Permit Description: INSTALL: A/C (APA)
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
06/20/2002 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Closed
Permit Number: T02ME00379
Permite Description: INSTALL: A/C (APA)
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/09/2002 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection 0999*MECHANICAL INSTALLATION OF EQUIPMENT APPROVED ACCEPTABLE EQUIPMENT LOCATED IN PLENIUM ABOVE GRID ABOVE CORRIDOR. SPACE DOES NOT CONFORM TO STANDARD. OF A PLENIUM. 1.) COMBUSTIBLE EXIST WALK WAYS BROCKING ETC. TO FAN COILS. 2.) HOLES IN RATED WALLS NEED TO BE SEALED. 3.) HOW IS FUTURE ACCESS TO FAN COILS GOING TO BE ACCOMPLISHED WHEN WALK WAYS REMOVED?? |