Permit: T02ME00126
Permit Details
Apply Date:
03/07/2002
Applicant:
RUSSETT SERVICE CORPORATION, *C
Description:
INSTALL:GAS PACK(APA)
Contractors:
- RUSSETT SERVICE CORPORATION, *C
Outstanding Activity Conditions
Permit Number - T02ME00126
Permit Status: Expired
Permit Description: INSTALL:GAS PACK(APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 03/07/2002 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T02ME00126
Permite Description: INSTALL:GAS PACK(APA)
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/14/2002 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection 0999*1.REMOVE UNION FROM GAS LINE ON ROOF. SEE SEC. 1211.10 1994 UPC 2. 1/2" GAS PIPE NOT ADEQUATE FOR 90,000 BTU 50' FROM METER. USE 3/4 THE ENTIRE LENGTH. 3.) PROVIDE A PRESSURE TEST ON GAS PIPING. |