Permit: T02EL02392
Permit Details
Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
301 E PASTIME RD #10
Address NEW:
301 E PASTIME RD #10
Apply Date:
12/10/2002
Applicant:
YOUNG VICTORIA
Description:
RECONNECT:ELECTRIC RV
Outstanding Activity Conditions
Permit Number - T02EL02392
Permit Status: Expired
Permit Description: RECONNECT:ELECTRIC RV
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/10/2002 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T02EL02392
Permite Description: RECONNECT:ELECTRIC RV
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/11/2002 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0999* 1.) PLEASE PROTECT LIFE LINE CORD AT OPENING TO RV AND AT EXPOSED CONDUCTORS. 2.) WE HAVE EXPOSED CONDUCTORS. 3.) PLUG ADAPTER IS FOR TEMPORARY USAGE NOT PERMANENT CONNECTION. 4.) USE AN APPROVED LIFE LINE NOT A LARGE EXTENTION CORD. 5.) REPAIR: RECEPETICALES AT FLOOR BY CLOSET. 6.) A SMOKE DETECTOR IS NEEDED. 7.) WE ARE MISSING FACE PLATE 8.) WE HAVE EXPOSED CONDUCTORS AT WATER HEATER. 9.) USE PROPER STRAW RELIEF CONNECTOR TO SUBPANEL EXSISTING PANEL IS UNDER SINK. |