08/15/2002
Applicant:
BLANKENBAKER ELECTRIC *C
Description:
UPGRADE: ELECTRICAL FROM 100AMP TO 200AMP (APA)
Contractors:
  • BLANKENBAKER ELECTRIC *C

Outstanding Activity Conditions

Permit Number - T02EL01683
Permit Status: Expired
Permit Description: UPGRADE: ELECTRICAL FROM 100AMP TO 200AMP (APA)
Total Outstanding Activity Conditions - 1
Date Name
08/15/2002 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T02EL01683
Permite Description: UPGRADE: ELECTRICAL FROM 100AMP TO 200AMP (APA)
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
08/19/2002 ELECTRIC - FINAL N/A Denied IVRS - Inspection 0245*1.) NEED TO VERIFY GAS BONDING 250-194 NEC. 2.) OVERHEAD SERVICE DROP TO COMPLY WITH 680-8 NEC. FOR CLEARANCE TO WATER LINE OF SPA. 3.) SPA SHOULD BE PROJECTED BY GFI BREAKER PER NEC. 680-42. 4.) UPON APPROVAL OF SERVICE INSTALLATION, CLEARANCE WILL BE SUBJECT TO COMPLIANCE WITH NOTE 2 & 3 ABOVE.