Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
6533 E 12TH ST
Address NEW:
6533 E 12TH ST
Apply Date:
08/15/2002
Applicant:
GAMBLE ELECTRIC INC''T''
Description:
UPGRADE:ELECTRICAL 100AMP TO 200AMP (APA)
Contractors:
  • GAMBLE ELECTRIC INC''T''

Outstanding Activity Conditions

Permit Number - T02EL01682
Permit Status: Expired
Permit Description: UPGRADE:ELECTRICAL 100AMP TO 200AMP (APA)
Total Outstanding Activity Conditions - 1
Date Name
08/15/2002 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T02EL01682
Permite Description: UPGRADE:ELECTRICAL 100AMP TO 200AMP (APA)
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
08/16/2002 ELECTRIC - FINAL N/A Denied IVRS - Inspection 0235*1.) GROUNDING INCOMPLETE, NEED TWO 5/8"X' GRD. RODS & COLD WTR & GAS PIPING GRD'D 2.) PANEL INDEX/DIRECTORY MUST BE COMPLETED. 3.) NOT LESS THAN TWO STRAPS NEED ON RISER PIPE BELOW ROOF.

Documents

File Name Document Type  
None DOCUMENTS VIEW