Permit: T02EL01089
Permit Details
Apply Date:
05/24/2002
Applicant:
MOFFITT ROBERT SIMPSON & MOFFITT
Description:
ELECTRIC:UPGRADE 100AMPS
Permit Reviews
Permit Number - T02EL01089
Permit Status: Expired
Permit Description: ELECTRIC:UPGRADE 100AMPS
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 05/24/2002 | ELECTRICAL | 05/24/2002 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T02EL01089
Permit Status: Expired
Permit Description: ELECTRIC:UPGRADE 100AMPS
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 05/24/2002 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T02EL01089
Permite Description: ELECTRIC:UPGRADE 100AMPS
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/16/2003 | ELECTRIC - SERVICE UPGRADE | N/A | Partial Approval | 1.) NEED PERMANENT METAL ADDRESS TAG. 2.) STRAP GROUND WIRE FIRMLY TO WALL. A REFEE IS DUE BEFORE THE NEXT INSPECTION. |
| 08/12/2002 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0210*THE ELECTRICAL PANEL IS INSTALLED HIGHER THAN CURRENT ELECTRICAL CODE ALLOWS. SEE DIAGRAM BELOW. THE COLD WATER PIPE AND GAS PIPE MUST ALSO BE BONDED TO THE ELECTRIC SERVICE. |