Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address NEW:
300 S TUCSON BL 01
Apply Date:
01/18/2002
Applicant:
MAJOR ELECTRIC INC,*C
Description:
ELECTRIC:NEW SERVICE 400AMPS
Contractors:
  • MAJOR ELECTRIC INC,*C

Permit Reviews

Permit Number - T02EL00116
Permit Status: Final
Permit Description: ELECTRIC:NEW SERVICE 400AMPS
Start Date Submittal Complete Date Status  
01/18/2002 ELECTRICAL 01/18/2002 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T02EL00116
Permit Status: Final
Permit Description: ELECTRIC:NEW SERVICE 400AMPS
Total Outstanding Activity Conditions - 1
Date Name
01/18/2002 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T02EL00116
Permit Description: ELECTRIC:NEW SERVICE 400AMPS
Total Completed Inspections - 3
Date Description Inspector Results Comments
01/28/2002 ELECTRIC - FINAL MCAPISTR Approved IVRS - Inspection 0000*
01/28/2002 ELECTRIC - FINAL DSANTACR Approved IVRS - Inspection 0245*NOTES 1.) CIC CABLE ALREADY INSTALLED PRIOR TO APPROVAL. 2.) GROUNDING ELECTRODE CONDUCTOR TO BE SIZED PER 250-66 NEC. 3.) ID CIRCUIT BREAKERS 4.) I.D. DISC. SWITCHES FOR AC UNITS. 230-70 NEC.
01/28/2002 ELECTRIC - CABLE DROP DSANTACR Approved IVRS - Inspection 0000*