Permit: T02CM03038
Permit Details
Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
115 E LIMBERLOST DR
Address NEW:
115 E LIMBERLOST DR
Apply Date:
06/24/2002
Applicant:
R W G CONSTRUCTION CO ,
Description:
REPLACE:A/C UNIT
Contractors:
- R W G CONSTRUCTION CO ,
Permit Reviews
Permit Number - T02CM03038
Permit Status: Expired
Permit Description: REPLACE:A/C UNIT
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 06/24/2002 | OTHER | 06/24/2002 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T02CM03038
Permit Status: Expired
Permit Description: REPLACE:A/C UNIT
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 06/24/2002 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T02CM03038
Permite Description: REPLACE:A/C UNIT
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| MECHANICAL - FINAL | N/A | Not Inspected | ||
| 07/15/2002 | MECHANICAL - INTERMEDIATE | N/A | Denied | IVRS - Inspection 0999*1.) INSIDE OF JOB NO ACCESS TO FURNACE 2.) 5 TON REMOTE A/C CONDENSER IMPROPER FUSING 3.) COMBUSTION AIR GRILL LOWER WALL NOT IN PLACE 4.) CONTROL WIRING DISCONNECTED. 5.) NO VISIBLE SIGN OF UPPER COMBUSTION DUCT. FURN VENT ON ROOF. PKG UNIT ON EAST SIDE OF STRUCT. ON SLAB. NEED SUN RAIN SHIELDS FLEX DUCT CONNECTORS 6.) NORTH SIDE OF HOUSE WATER HTR. ROOM A.) 7 & P VALVE NEED RELIEF LINE. B.) NO UPPER COMBUSTION OPENING IN ROOM, 10 SQ MIN. C IMPROPER B-1 VNET TERMINATION. |