Permit Details

Status:
Withdrwn
Type:
COMMERCIAL ADDITION
Address:
3350 E GRANT RD
Apply Date:
01/09/2002
Applicant:
N/A
Description:
INSTALL:3 DENTAL CHAIRS
Architects:
  • STEPHEN LEON MOOS
Contractors:
  • SCHNEIDER BROTHERS CONSTRUCTION

Permit Reviews

Permit Number - T02CM00123
Permit Status: Withdrwn
Permit Description: INSTALL:3 DENTAL CHAIRS
Start Date Submittal Complete Date Status  
01/09/2002 OTHER 01/10/2002 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T02CM00123
Permit Status: Withdrwn
Permit Description: INSTALL:3 DENTAL CHAIRS
Total Outstanding Activity Conditions - 1
Date Name
01/09/2002 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Withdrwn
Permit Number: T02CM00123
Permite Description: INSTALL:3 DENTAL CHAIRS
Total Outstanding Inspections - 6
Last Inspection Date Description Inspector Results Comments
BOILER - AIR TANK N/A Not Inspected
01/24/2002 ELECTRIC - UNDERGROUND N/A Denied IVRS - Inspection 0245*NEED TO INSPECT CONDUIT RUN ABOVE CEILING ELECTRICAN TO MEET INSPECTOR TOMORROW AM PER CONVERSATION WITH KIETH S.
01/24/2002 ELECTRIC - INTERMEDIATE N/A Denied IVRS - Inspection 0245*
01/25/2002 PLUMBING - INTERMEDIATE N/A Partial Approval IVRS - Inspection 0000*1.) AIR PRESSURE TEST FOR WATER & VAC LINES OK .2) NOTE: MUST ANCHOR COPPER WATER LINE.
01/28/2002 ELECTRIC - ABOVE CEILING N/A Denied IVRS - Inspection 0245*NOTES CONTR. USED EXISTING CIRCUITS DOES NOT COMPLY WITH REQUIREMENTS OF 517 NEC. BECAUSE HOME RUNS BAACK TO PANEL NOT USING METALIC RACEWAY.
02/22/2002 PLUMBING - FINAL N/A Denied 1.)MUST PROVIDE LISTING FOR VACCUME PUMP ON WATER SUPPLY AIR BREAK AND VACCUME BREAKERS.

Completed Inspections

Permit Status: Withdrwn
Permit Number: T02CM00123
Permit Description: INSTALL:3 DENTAL CHAIRS
Total Completed Inspections - 3
Date Description Inspector Results Comments
01/25/2002 PLUMBING - PROGRESS TRINIVJR Approved IVRS - Inspection 0000*
02/22/2002 BOILER FINAL CWILLIAM Approved IVRS - Inspection 0000*UNFIRED PRESS. VESSELL.
02/22/2002 ELECTRIC - FINAL DSANTACR Approved IVRS - Inspection 0000*CONTRACTOR TO RECALL WHEN ON SITE TO WALK THRU WITH INSPECTOR TO EXPOSE CEILING TO INSPECT CONDUIT ROUTING.

Documents

File Name Document Type  
None DOCUMENTS VIEW