Permit Details

Status:
Expired
Type:
SIGN PERMIT
Address:
4066 E 22ND ST
Apply Date:
12/11/2001
Applicant:
SIGN CENTER
Description:
SIGN:ELECTRIC:3426
Contractors:
  • SIGN CENTER

Outstanding Inspections

Permit Status: Expired
Permit Number: T01OT01073
Permite Description: SIGN:ELECTRIC:3426
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
12/26/2001 SIGN ELECTRIC N/A Denied IVRS - Inspection 0999*1.) ALL FLEX CONDUIT IN EXCESS OF 3 1/2" LONG MUST BE SECURED WITHIN 12" OF EACH MUST BE SECURED WITHIN 12" OF EACH TERMINATION AND FOR EVERY 3 1/2' OF LENGTHS 2.) ALL PULL BOXES MUST BE PROPERLY SECURED. 3.) COMPLETE PRIMARY WIRING & REPLACE J-BOX COVER 4.) REPLACE COVER ON TANSFORMER BOX 5.) REPLACE COVER ON TRANSFORMER BOX 6.) ALL CONDUIT NIPPLES AND CONDUIT ENDS MUST BE FIRMLY ATTACHED. NIPPLES ARE TO BE INSTALLED WRENCH LIGHT.

Completed Inspections

Permit Status: Expired
Permit Number: T01OT01073
Permit Description: SIGN:ELECTRIC:3426
Total Completed Inspections - 3
Date Description Inspector Results Comments
12/18/2001 SIGN SITE REVIEW JYBARRA Approved
12/21/2001 SIGN SHOP LHANLY Approved IVRS - Inspection 0000*
12/26/2001 SIGN INSPECTION DJOHNSTO Approved IVRS - Inspection 0000*

Documents

File Name Document Type  
None SIGNS VIEW