Permit: T01OT00639
Permit Details
Apply Date:
09/28/2001
Applicant:
BOB'S NEON
Description:
SIGN:3112
Contractors:
- BOB'S NEON
Outstanding Inspections
Permit Status: Expired
Permit Number: T01OT00639
Permite Description: SIGN:3112
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/31/2001 | SIGN ELECTRIC | N/A | Denied | IVRS - Inspection 0999*SIGN IS INSTALLED OK BUT. 1.) NEC 600-5 EACH COMMERCIAL OCCUPANCY SHALL BE PROVIDED WITH AN OUTLET FOR A SIGN LIGHTING SYSTEM. THE OUTLET SHALL BE SUPPLIED BY A 20A BRANCH CIRCUIT THAT SUPPLIES NO OTHER LAND. 2.) SIGN MAY NOT BE CONNECTED TO THE CANOPY LIGHTING SYSTEM. A LICENSED ELECTRICIAN WILL NEED TO PROVIDE THE OUTLET (SEE ITEMS) FOR SIGN COMPANY TO MAKE PROPER CONNECTIONS. 3.) CURRENT SIGN IS ORDERED TO BE DISCONNECTED UNTIL SUCH TIME AS PROPER OUTLET HAS BEEN PROVIDED. |
Completed Inspections
Permit Status: Expired
Permit Number: T01OT00639
Permit Description: SIGN:3112
Total Completed Inspections - 3
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/01/2001 | SIGN SITE REVIEW | JSONKIN | Approved | IVRS - Inspection 0000* |
10/24/2001 | SIGN SHOP | LHANLY | Approved | IVRS - Inspection 0000* |
10/24/2002 | SIGN INSPECTION | DJOHNSTO | Approved | IVRS - Inspection 0000* |