Permit: T01OT00027
Permit Details
Apply Date:
02/05/2001
Applicant:
CHARLIE BEST
Description:
GROUP INSPECTION
Outstanding Activity Conditions
Permit Number - T01OT00027
Permit Status: Withdrwn
Permit Description: GROUP INSPECTION
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 02/05/2001 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Withdrwn
Permit Number: T01OT00027
Permite Description: GROUP INSPECTION
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/05/2001 | PLUMBING - FINAL | N/A | Correction Required | GROUP INSP. RESULTS:PLUMBING: NOT READY; 1)PVC WATER PIPING IN EXPOSED EXTERIOR LOCATIONS NOT ALLOWED. NO VACUUM BREAKERS ON HOSE BIB,PIPING NOT SUPPORTED. 2) WASTE PIPING FOR EWC NOT TO CODE. 3) WASTE PIPING FOR SS SINK A) TRAP ARM TOO LONG B) ABS NOT APPROVED IN EXPOSED EXTERIOR LOCATION C) VENT NOT CONNECTED. 4) NO SHAFT ON ELEC. WATER HEATER; NO T AND P DRAIN 5) SHOWER DRAIN NOT CAULKED 6) CERTIFICATION FOR RPBP. |
| 08/17/2001 | ELECTRIC - FINAL | N/A | Correction Required | PROGRESS OK. NEED TO CHECK W/REGISTRAR OFFICE FOR LICENSE INFORMATION. NEED APPROVED PLAN FOR MINOR ELECTRICAL AT BOTH OCCUPANCIES. |
Completed Inspections
Permit Status: Withdrwn
Permit Number: T01OT00027
Permit Description: GROUP INSPECTION
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2001 | MECHANICAL - FINAL | JMILITEL | Approved | OLD EQUIPMENT HAS BEEN REMOVED. REMAINING COOLERS ARE OK AS IS. |
| 08/17/2001 | BUILDING - FINAL | DWITT | Approved | |
| 08/17/2001 | BUILDING - FINAL | DWITT | Approved | REMOVE BARRICADE BAR AND HASP FROM EXITS. |