Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Apply Date:
02/20/2001
Applicant:
KELLY AIR CONDITIONING , *C
Description:
GASPACK:REPLACEMENT(APA)
Contractors:
  • KELLY AIR CONDITIONING , *C

Outstanding Activity Conditions

Permit Number - T01ME00154
Permit Status: Expired
Permit Description: GASPACK:REPLACEMENT(APA)
Total Outstanding Activity Conditions - 1
Date Name
02/20/2001 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T01ME00154
Permite Description: GASPACK:REPLACEMENT(APA)
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
02/21/2001 MECHANICAL - FINAL N/A Denied IVRS - Inspection 0999* 1) YOU CANNOT USE PLUMBERS TAPE TO STRAP FLEX DUCT. HANGER STRAP SHALL BE MINIMUM 1 1/2" 2) STRAP FLEX DUCT UP OFF OF DIRT. STRAPS SHALL BE MAX 4' APART. 3) INSULATE BARE METAL ON T-WYES CORRECT AND RECALL FOR FINAL