Description:
SERVICE:REPLACE SERVICE PANEL T01VL02286
Permit Reviews
Permit Number - T01EL02405
Permit Status: Expired
Permit Description: SERVICE:REPLACE SERVICE PANEL T01VL02286
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 09/26/2001 | ELECTRICAL | 09/26/2001 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T01EL02405
Permit Status: Expired
Permit Description: SERVICE:REPLACE SERVICE PANEL T01VL02286
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 09/26/2001 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T01EL02405
Permite Description: SERVICE:REPLACE SERVICE PANEL T01VL02286
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/26/2001 | ELECTRIC - SERVICE UPGRADE | N/A | Denied | IVRS - Inspection 0245*DENIED NOTES FOLLOW UP PLEASE APPEARS TENANT INSTALLED A LOAD CENTER WITH A HIGHER AMPACITY THAN EXISTING SERVICE IS ORIGINALLY DESIGNED FOR. 1.) MUST HAVE A LICENSED CONTR. DO WORK. 2.) OBTAIN PROPER PERMIT WITH LOAD CALC'S FOR SERVICE UPGRADE. 3.) NEW LOAD CENTER WAS NOT INSTALED PROPERLY, CANNOT OPEN COVER, IN THE EVENT OF EMERGENCY, WOULD NOT BE ABLE TO SHUT OFF POWER. 72 HOURS (3DAYS) TO COMPLY OR POWER WILL BE DISCONNECTED. |