Permit: T01EL01637
Permit Details
Apply Date:
06/25/2001
Applicant:
KELLY ELECTRIC COMPANY INC *C
Description:
UPGRADE:ELECTRIC 100-200 AMP (APA)
Contractors:
- KELLY ELECTRIC COMPANY INC *C
Outstanding Activity Conditions
Permit Number - T01EL01637
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC 100-200 AMP (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 06/25/2001 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T01EL01637
Permite Description: UPGRADE:ELECTRIC 100-200 AMP (APA)
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/28/2001 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0245*1.) PROVIDE OR INSTALL RISER SUPPORT WITHIN 3' OF SERVICE ENCLOSURE. 2.) GROUND J-BOX BELOW PANEL PER 250-148 N.E.C 3.) INSTALL BOND BUSHING ON 2" NIPPLE OR BONDING LOCK PER 250-94 4.) INSTALL PERMANENT ADDRESS LABELS PER 230-70 NEC #9287 CITY AMEND. 5.) PLASTIC BUSHING I J-BOX BELOW PANEL NOT INSTALLED PROPERLY. 6.) SUPPORT 3/4" CONDUIT BELOW PANEL. |