Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
2901 E MABEL ST
Address NEW:
2901 E MABEL ST
Apply Date:
06/25/2001
Applicant:
KELLY ELECTRIC COMPANY INC *C
Description:
UPGRADE:ELECTRIC 100-200 AMP (APA)
Contractors:
  • KELLY ELECTRIC COMPANY INC *C

Outstanding Activity Conditions

Permit Number - T01EL01637
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC 100-200 AMP (APA)
Total Outstanding Activity Conditions - 1
Date Name
06/25/2001 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T01EL01637
Permite Description: UPGRADE:ELECTRIC 100-200 AMP (APA)
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
06/28/2001 ELECTRIC - FINAL N/A Denied IVRS - Inspection 0245*1.) PROVIDE OR INSTALL RISER SUPPORT WITHIN 3' OF SERVICE ENCLOSURE. 2.) GROUND J-BOX BELOW PANEL PER 250-148 N.E.C 3.) INSTALL BOND BUSHING ON 2" NIPPLE OR BONDING LOCK PER 250-94 4.) INSTALL PERMANENT ADDRESS LABELS PER 230-70 NEC #9287 CITY AMEND. 5.) PLASTIC BUSHING I J-BOX BELOW PANEL NOT INSTALLED PROPERLY. 6.) SUPPORT 3/4" CONDUIT BELOW PANEL.