Permit: T01EL01334
Permit Details
Apply Date:
05/29/2001
Applicant:
MAJOR ELECTRIC INC,*C
Description:
ELECT:UPGRADE FROM 100 AMPS TO 200 AMPS(APA)
Contractors:
- MAJOR ELECTRIC INC,*C
Outstanding Activity Conditions
Permit Number - T01EL01334
Permit Status: Expired
Permit Description: ELECT:UPGRADE FROM 100 AMPS TO 200 AMPS(APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 05/29/2001 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T01EL01334
Permite Description: ELECT:UPGRADE FROM 100 AMPS TO 200 AMPS(APA)
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/04/2001 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0245*1)PLUG BREAKER OK ON FRONT.2)I.D. CIRCUIT BREAKERS.3)BOND GAS PIPING, VERTIFY WATER BOND TO PANEL, 250-104 N.E.C.4)PROVIDE BOND BUSHINGS WHERE CONCENTRIC KO'S ARE USED, PER ART 250 N.E.C. 5)PROVIDE CONNECTORS WITH BUSHED ENDS WHERE CABLE EXITS CONDUITS.300-15 THRU 16 NEC.6)IMPROPER WIRING METHODS FOR SINGLE CONDUCTORS EXITING CONDUIT, UNDER HOUSE.USE J-BOXES ETC. |