Permit: T01EL01083
Permit Details
Apply Date:
05/03/2001
Applicant:
FEDORA ELECTRIC
Description:
ELECTRIC:UPGRADE 100-200AMPS
Contractors:
- FEDORA ELECTRIC
Permit Reviews
Permit Number - T01EL01083
Permit Status: Final
Permit Description: ELECTRIC:UPGRADE 100-200AMPS
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 05/03/2001 | ELECTRICAL | 05/03/2001 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T01EL01083
Permit Status: Final
Permit Description: ELECTRIC:UPGRADE 100-200AMPS
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 05/03/2001 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T01EL01083
Permit Description: ELECTRIC:UPGRADE 100-200AMPS
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/15/2001 | ELECTRIC - CABLE DROP | DSANTACR | Approved | IVRS - Inspection 0000* 1)INSTALL BOND BUSHING OR GROUND CLAMP AT THE END OF 3/4" WHERE GROUNDING ELECTRODE CONDUCTORS ARE EXITING.2)CHASE NIPPLES NOT ALLOWED,USE CLOSET NIPPLE WITH LOCKNUT BOTH ENDS.3)SUPPORT 3/4".4)INSTALL PERMANENT ADDRESS LABEL,SCREWED OR RIVITED TO ENCLOSURE. |
| 05/18/2001 | ELECTRIC - FINAL | RMAJUTA | Approved | IVRS - Inspection 0000* |
| 05/18/2001 | ELECTRIC - SERVICE UPGRADE | RMAJUTA | Approved | IVRS - Inspection 0000* |