Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Closed
Type:
COMMERCIAL OTHER
Apply Date:
04/13/2001
Applicant:
SAM SIEBENBERG
Description:
ELECTRICAL: POWER RECONNECT

Outstanding Activity Conditions

Permit Number - T01EL00882
Permit Status: Closed
Permit Description: ELECTRICAL: POWER RECONNECT
Total Outstanding Activity Conditions - 1
Date Name
04/13/2001 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Closed
Permit Number: T01EL00882
Permite Description: ELECTRICAL: POWER RECONNECT
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
04/18/2001 ELECTRIC - FINAL N/A Denied IVRS - Inspection 0999* 1) REPAIR OR REMOVE BROKEN AND OPEN BOX - FRONT /WEST
2) MISSING FALE PLATES 3) INSTALL LOOSE HANGING LIGHT FIXTURE 4) RE ATTACH OUTLETS AND CONDUIT TO WALL 5) FURNACE NEED FUSE PROTECTION - FUSE STAT CORD TO BE INSTALLED CORRECTLY 6) FILL ALL UNUSED OPENINGS IN BOXES 7) REMOVE IMPROPERLY WIRED ELECTRIC IN BACK 8) DOUBLE LUGING AT SERVICE DISCONNECT
9) NEED LICENCED ELECTRICAL L-11 CONTRACTOR TO CHECK SERVICE AND REPAIR ALL WORK
10) NEED GENERAL REPAIR PERMIT FOR BLDG AND PLBG INSP.
04/18/2001 FIRE - FINAL N/A Denied

Documents

File Name Document Type  
None DOCUMENTS VIEW