Permit: T01EL00667
Permit Details
Apply Date:
03/21/2001
Applicant:
EGAN SCOTT D & JONES-EGAN PERNEL
Description:
ELECTRIC:NEW METER INSTALL
Outstanding Activity Conditions
Permit Number - T01EL00667
Permit Status: Expired
Permit Description: ELECTRIC:NEW METER INSTALL
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 03/21/2001 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T01EL00667
Permite Description: ELECTRIC:NEW METER INSTALL
Total Outstanding Inspections - 3
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| ELECTRIC - CABLE DROP | N/A | Not Inspected | ||
| ELECTRIC - FINAL | N/A | Not Inspected | ||
| 03/22/2001 | ELECTRIC - SERVICE UPGRADE | N/A | Denied | IVRS - Inspection 0999* 1) NEED PERMANENT METAL ADDRESS LABEL 2) LABEL BREAKERS 3) VERIFY GROUNDING ELECTRODE SYSTEM 4) BOND GAS AND WATER 5) USE CORRECT SIZE GROUNDING EQUIPMENT CONDUCTOR 6) BOND AROUND CONCENTRIC KNOCK OUTS 7) SUPPORT CONDUITS AS PER CODE 8) CORRECTLY SUPPORT RISER 9) NEED GUY BACK BRACE ON RISER 10) NEED ACCESS TO OTHER END OF 1" CONDUIT 11) VERIFY WHO IS DOING ELECTRICAL WORK |