| 02/16/2001 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Closed
Permit Number: T01EL00360
Permite Description: RECONNECT:ELECTRIC:TUTORING OFFICES
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/05/2001 | ELECTRIC - RECONNECT | N/A | Denied | IVRS - Inspection 0999* 1) THE BLDG MUST BE OPENED FOR THIS TYPE OF INSP. 2) THE BLDG SERVICE MUST HAVE A PERMANENT ADDRESS LABLE ON IT INDICATING 934 N MAIN AVE NO INK 3) THE MAIN 60AMP DISCONNECT MUST BE CLEANED UP ALL DOUBLE LUGGING IS TO BE REMOVED AND LINE AND LOAD AND NEUTRAL CONNECTIONS 4) A QUALIFIED ELECTRICIAN IS TO TAPE THE EXPOSED CONNECTION BETWEEN OWNER AND TEP LINES ABOVE SERVICE THE EXPOSED CONNECTIONS ARE TOO LOW TO LEAVE EXPOSED 5) WIRING METHODS OUTSIDE ENTRY TO BE CORRECTED OR REMOVED |