Permit Details

Status:
Closed
Type:
COMMERCIAL OTHER
Address:
934 N MAIN AV
Address NEW:
934 N MAIN AV
Apply Date:
02/16/2001
Applicant:
RANISON KENNEDY
Description:
RECONNECT:ELECTRIC:TUTORING OFFICES

Outstanding Activity Conditions

Permit Number - T01EL00360
Permit Status: Closed
Permit Description: RECONNECT:ELECTRIC:TUTORING OFFICES
Total Outstanding Activity Conditions - 1
Date Name
02/16/2001 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Closed
Permit Number: T01EL00360
Permite Description: RECONNECT:ELECTRIC:TUTORING OFFICES
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
03/05/2001 ELECTRIC - RECONNECT N/A Denied IVRS - Inspection 0999* 1) THE BLDG MUST BE OPENED FOR THIS TYPE OF INSP. 2) THE BLDG SERVICE MUST HAVE A PERMANENT ADDRESS LABLE ON IT INDICATING 934 N MAIN AVE NO INK 3) THE MAIN 60AMP DISCONNECT MUST BE CLEANED UP ALL DOUBLE LUGGING IS TO BE REMOVED AND LINE AND LOAD AND NEUTRAL CONNECTIONS 4) A QUALIFIED ELECTRICIAN IS TO TAPE THE EXPOSED CONNECTION BETWEEN OWNER AND TEP LINES ABOVE SERVICE THE EXPOSED CONNECTIONS ARE TOO LOW TO LEAVE EXPOSED 5) WIRING METHODS OUTSIDE ENTRY TO BE CORRECTED OR REMOVED

Documents

File Name Document Type  
None DOCUMENTS VIEW