Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Apply Date:
01/24/2001
Applicant:
BROWN AMUSEMENTS
Description:
CARNIVAL:ELECTRIC

Permit Reviews

Permit Number - T01EL00162
Permit Status: Final
Permit Description: CARNIVAL:ELECTRIC
Start Date Submittal Complete Date Status  
01/24/2001 ELECTRICAL 01/24/2001 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T01EL00162
Permit Status: Final
Permit Description: CARNIVAL:ELECTRIC
Total Outstanding Activity Conditions - 1
Date Name
01/24/2001 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T01EL00162
Permit Description: CARNIVAL:ELECTRIC
Total Completed Inspections - 2
Date Description Inspector Results Comments
01/26/2001 PERMIT FINALED MCAPISTR Approved
01/26/2001 ELECTRIC - FINAL JORTA Approved IVRS - Inspection 0999*
MUST HAVE CABLE RAMPS ON EACH AREA WHERE CABLES ARE STRUNG ALONG PED. OR VEHICAL TRAFFIC.
USE PROPER TERMINATION LUGS TO CONNECT STRANDED CABLE ONTO DISTRIBUTION BOXER AND THE LIHE
FERRIS WHEEL
EXPOSED SINGLE CONDUCTORS, TERINATE GROUNDING STRIP PROPERLY INTO PANEL BOARD
MUST HAVE BALLOUT IN PROPER ENCLOSURE
INSTALL PROPER LENSE ON ALL FIXTURES TO MAINTAIN RAINTIGHT INTEGRITY
NOTE FOR ONE TIME ONLY YOU MAY FASTEN PARALLED 2X4 OR ? W/A SUITABLE COVER FOR ITEM #1 BI-LEVEL SIDES TO ASSEMBLE THE MANUFACTURED PITCH