Permit: T01EL00111
Permit Details
Status:
Withdrwn
Type:
SINGLE FAMILY OTHER
Address:
1854 W SAN JUAN TR
Address NEW:
1854 W SAN JUAN TR
Apply Date:
01/17/2001
Applicant:
EATHON BUTLER
Description:
UPGRADE:ELECTRIC FROM 60AMP TO 200AMP
Permit Reviews
Permit Number - T01EL00111
Permit Status: Withdrwn
Permit Description: UPGRADE:ELECTRIC FROM 60AMP TO 200AMP
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 01/17/2001 | ELECTRICAL | 01/17/2001 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T01EL00111
Permit Status: Withdrwn
Permit Description: UPGRADE:ELECTRIC FROM 60AMP TO 200AMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 01/17/2001 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Withdrwn
Permit Number: T01EL00111
Permite Description: UPGRADE:ELECTRIC FROM 60AMP TO 200AMP
Total Outstanding Inspections - 3
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/21/2001 | ELECTRIC - CABLE DROP | N/A | Denied | IVRS - Inspection 0999* 1. NEED PERMANENT METAL ADDRESS LABEL 2. BOND GAS 250-104 3. HIGHEST AVAILABLE BREAKER NOT OVER 6'7" 380-8 4. WORKING CLEARENCE VIOLATION 110-26 5. VERIFY LICENSED ELECTRICAL CONTRACTOR |
| 01/21/2001 | ELECTRIC - SERVICE UPGRADE | N/A | Denied | IVRS - Inspection 0999* 1. NEED PERMANENT METAL ADDRESS LABEL 2. BOND GAS 250-104 3. HIGHEST AVAILABLE BREAKER NOT OVER 6' 7" 380-8 4. WORKING CLEARENCE VIOLATION 110-26 5. VERIFY LICENSED ELECTRICAL CONTRACTOR |
| 01/30/2001 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0999* NEED LICENSED CONTRACTOR IN VIOLATION OF CLEARANCE 110-26 |