Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Apply Date:
08/24/2000
Applicant:
TLC PLUMBING
Description:
WATER HEATER:REPLACEMENT
Contractors:
  • TLC PLUMBING

Outstanding Activity Conditions

Permit Number - T00PL01606
Permit Status: Expired
Permit Description: WATER HEATER:REPLACEMENT
Total Outstanding Activity Conditions - 1
Date Name
08/24/2000 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T00PL01606
Permite Description: WATER HEATER:REPLACEMENT
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
PLUMBING - FINAL N/A Not Inspected

Documents

File Name Document Type  
None DOCUMENTS VIEW