Permit Details

Status:
Closed
Type:
COMMERCIAL OTHER
Address NEW:
3351 E HEMISPHERE LP
Apply Date:
10/04/2000
Applicant:
DEJEAN KAREN/BILL
Description:
CERTIFICATE OF OCCUPANCY: WAREHOUSE/OFFICE

Permit Reviews

Permit Number - T00OT00250
Permit Status: Closed
Permit Description: CERTIFICATE OF OCCUPANCY: WAREHOUSE/OFFICE
Start Date Submittal Complete Date Status  
10/04/2000 C OF O 10/04/2000 COMPLETED Review Details

Outstanding Inspections

Permit Status: Closed
Permit Number: T00OT00250
Permite Description: CERTIFICATE OF OCCUPANCY: WAREHOUSE/OFFICE
Total Outstanding Inspections - 5
Last Inspection Date Description Inspector Results Comments
SIGN - FINAL N/A Not Inspected
10/12/2000 BUILDING - FINAL N/A Not ready for Inspection IVRS - Inspection 0000*
CHANGE DOOR AT TOILET ROOM
ASK ARCHITECT TO CLARIFY THE SQUIGGELY LINE AT THE ROOM BY THE STORE ROOM/ WAREHOUSE
NAME THE ROOMS OCCUPANCY, TYPE OF CONST OCCUPANCY LOAD, ETC.
10/12/2000 ELECTRIC - FINAL N/A Partial Approval IVRS - Inspection 0000*
REMOVE EMPTY ELECTRICAL CONDUIT AND WIRING AT EXTERIOR GATED STORAGE/ EPMT. AREA.
INSTALL KNOCK OUT SEALS ON ALL OPEN CONDUIT TERMINATION HOLES IN CEILING ELECTRICAL BOXES
RECALL AT YOUR CONVENIENCE WHEN ALL OF ABOVE IS CORRECTED
10/12/2000 MECHANICAL - FINAL N/A Partial Approval IVRS - Inspection 0000*
STRAP FLEX DUCT EVERY 4'. STRAP OR ANCHOR ANY DIFFUSER OVER 25 LBS
REPAIR CONDENSATE DRAINS ON ROOF BLOCK EVERY 4' PAINT PVC W/LATEX PAINT. EXTEND DRAINS TO WITHIN 6" OF GROUND. INSTALL CONDENSATE DRAINS ON PACKAGE UNITS
MAKE NECESSARY CORRECTIONS AND RECALL
10/12/2000 FIRE - FINAL N/A Denied FIRE SPRINKLER COVERAGE IS NOT CORRECT,CEILING TILES/GRID MUST BE IN PLACE