Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
1639 N OLD RANCH RD
Apply Date:
10/26/2000
Applicant:
OROZCO BROTHERS HEATING AND COOL
Description:
INSTALL:HVAC
Contractors:
  • OROZCO BROTHERS HEATING AND COOL

Permit Reviews

Permit Number - T00ME01218
Permit Status: Expired
Permit Description: INSTALL:HVAC
Start Date Submittal Complete Date Status  
10/26/2000 MECHANICAL 10/26/2000 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T00ME01218
Permit Status: Expired
Permit Description: INSTALL:HVAC
Total Outstanding Activity Conditions - 1
Date Name
10/26/2000 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T00ME01218
Permite Description: INSTALL:HVAC
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
12/01/2000 MECHANICAL - INTERMEDIATE N/A Denied REJECTED
WHAT TYPE DUCT INSULATION WAS USED AS LINER?
PLASTIC CONDENSATE DRAIN IMPROPER TERMINATION, NOT PAINTED AND NO DRAIN
1/2" X 24" FLEX GAS LINE INCORRECT SIZE FOR 115,000 BTUH.
EXPOSED FLEX DUCT CONNECTIONS
EXPOSED CONTROL WIRING
CORRECTIONS ARE NEEDED TO MADE THIS JOB ACCEPTABLE
12/04/2000 MECHANICAL - FINAL N/A Denied IVRS - Inspection 0999*