Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
3125 N CHERRY AV
Address NEW:
3125 N CHERRY AV
Apply Date:
12/22/2000
Applicant:
D S ELECTRIC ''T''
Description:
ELEC:UPGRADE:60-100AMP(APA)
Contractors:
  • D S ELECTRIC ''T''

Outstanding Activity Conditions

Permit Number - T00EL02927
Permit Status: Expired
Permit Description: ELEC:UPGRADE:60-100AMP(APA)
Total Outstanding Activity Conditions - 1
Date Name
12/22/2000 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T00EL02927
Permite Description: ELEC:UPGRADE:60-100AMP(APA)
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
12/26/2000 ELECTRIC - FINAL N/A Denied IVRS - Inspection 0999*
WORKING CLEARENCES INFRONT OF PANEL 110-26
NEED 2 STRAPS BELOW ROOF ON RISER
NEED GAS BOND
VERIFY WATER BOND
LABEL BREAKERS

Documents

File Name Document Type  
None DOCUMENTS VIEW