Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Closed
Type:
COMMERCIAL OTHER
Address:
1225 S CHERRY AV
Address NEW:
1225 S CHERRY AV
Apply Date:
12/19/2000
Applicant:
TONY STREET
Description:
ELECTRIC SERVICE:RECONNECT

Outstanding Activity Conditions

Permit Number - T00EL02908
Permit Status: Closed
Permit Description: ELECTRIC SERVICE:RECONNECT
Total Outstanding Activity Conditions - 1
Date Name
12/19/2000 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Closed
Permit Number: T00EL02908
Permite Description: ELECTRIC SERVICE:RECONNECT
Total Outstanding Inspections - 4
Last Inspection Date Description Inspector Results Comments
ELECTRIC - FINAL N/A Not Inspected
FIRE - FINAL N/A Not Inspected
01/03/2001 ELECTRIC - PROGRESS N/A Partial Approval JIM GOLDIE OF GOLDIE ELECTRIC WILL BE L-11 DOING ELECTRICAL WORK.
NEED TO HAVE PLANS AND PERMIT FOR SERVICCE UPGRADE AT LOCATION
MUST HAVE LICSENED CONTRACTOR OF RECORD DOING WORK
12/21/2000 ELECTRIC - RECONNECT N/A Denied IVRS - Inspection 0999*
FULL ALL UNUSED OPENINGS IN PANEL
USE APPROVED SPLICE CONNECTORS
SOLID WIRE LARGER THAN #8 NOT ALLOWED IN RACEWAY SYSTEM
ATTACH PANEL COVER CORRECTLY
REMOVE CORD THRU WALL/WINDOR
EXCESSIVE PAINT IN RECPTICLES
MISSING FACEPLATE
MISSING FIXTURE
EXPOSED CONDUTORS
SECURE ALL CONDUITS PER CODE
VERIFY LICENSED L-11 ELECTRICAL CONTRACTOR