Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address:
262 N MAIN AV
Apply Date:
12/14/2000
Applicant:
STEPHEN T GREDE
Description:
INSTALL:ELECTRIC FIXTURES/PUMP
Architects:
  • GREDE, STEPHEN THOMAS
Contractors:
  • EDWARDS ELECTRICAL SYSTEMS INC ,

Permit Reviews

Permit Number - T00EL02865
Permit Status: Expired
Permit Description: INSTALL:ELECTRIC FIXTURES/PUMP
Start Date Submittal Complete Date Status  
12/14/2000 ELECTRICAL 12/14/2000 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T00EL02865
Permit Status: Expired
Permit Description: INSTALL:ELECTRIC FIXTURES/PUMP
Total Outstanding Activity Conditions - 1
Date Name
12/14/2000 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T00EL02865
Permite Description: INSTALL:ELECTRIC FIXTURES/PUMP
Total Outstanding Inspections - 3
Last Inspection Date Description Inspector Results Comments
ELECTRIC - FINAL N/A Not Inspected
01/11/2001 ELECTRIC - UNDERGROUND N/A Partial Approval IVRS - Inspection 0000*
CONDUIT DEPTH TO MEET REQUIREMENTS OF ART 300-5 NEED TO SEE CONCRETE ENCASEMENT
EMT CONDUIT ENCASED INCONCRETE IN WALLS NOT PROTECTED AGAINST CORROSION 300-16 (B)
OK PVC IN WALL
01/16/2001 ELECTRIC - INTERMEDIATE N/A Partial Approval IVRS - Inspection 0000*
OK BLOCK WALLS, PLEASE PULL GROUNDING EQUIPMENT CONDUTOR IN ALL CONDUITS