Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Apply Date:
12/01/2000
Applicant:
BOB'S NEON
Description:
SIGN:ELECTRIC:1736

Outstanding Activity Conditions

Permit Number - T00EL02768
Permit Status: Expired
Permit Description: SIGN:ELECTRIC:1736
Total Outstanding Activity Conditions - 1
Date Name
12/01/2000 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T00EL02768
Permite Description: SIGN:ELECTRIC:1736
Total Outstanding Inspections - 3
Last Inspection Date Description Inspector Results Comments
SIGN INSPECTION N/A Not Inspected
12/07/2000 SIGN SHOP N/A Denied IVRS - Inspection 0999*
NO SHUT OFF SWITCH
NO EQUIPMENT GROUND
FAULTY BALLAST
12/07/2000 SIGN ELECTRIC N/A Denied IVRS - Inspection 0999*
NO EQUIPMENT GROUND
NON WATER TIGHT SEAL WHERE FLEX PASSES THROUGH WALL
NO WATER TIGHT JUNCTION BOX ON ROOF
HAZARDOUS SUB STANDARD ELECTRIC AT SITE
SIGN CIRCUIT NOT IDENTIFIED AT SUB PANEL

Documents

File Name Document Type  
None SIGNS VIEW