Description:
RECONNECT:ELECTRIC-LAUNDRY ROOM

Outstanding Activity Conditions

Permit Number - T00EL02202
Permit Status: Expired
Permit Description: RECONNECT:ELECTRIC-LAUNDRY ROOM
Total Outstanding Activity Conditions - 1
Date Name
09/14/2000 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T00EL02202
Permite Description: RECONNECT:ELECTRIC-LAUNDRY ROOM
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
09/15/2000 ELECTRIC - RECONNECT N/A Denied IVRS - Inspection 0245*
INSTALL PERMANENT ADDRESS ON NEW SERVICE
BOND PER NEC 250/230
SUPPORT CONDUIT FROM GUTTER TO METER
EMT CONDUIT CANNOT SPAN HORIZONTAL MORE THAN 10' WITHOUT SUPPORT
VERIFY L-11 LICENSED CONTRACTOR
10/06/2000 ELECTRIC - FINAL N/A Denied IVRS - Inspection 0245*
A LICENSED C-11 ELECTRICAL CONTRACTOR REQUIRED TO DO WORK CALL 791-5550 EXT 136 AND LEAVE NAME OF CONTRACTOR
A PERMIT IS REQUIRED FOR REPLACEMENT OF SERVICE
BREAKER BOX AND REWIRE OF LAUNDRY
DOUBLE LUGGING
DERATING OF CONDUCTOR APPLICABLE
NEED TO WRAP EMT IN CONCRETE
NEED MAIN BREAKER NEW WIRING
EXPOSE ALL WIRING RE-FEE DUE