Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T00EL01323
Permit Details
Apply Date:
05/30/2000
Applicant:
CITY OF TUCSON/FRANK ELLIOTT
Description:
SERVICE:ADD PANEL/TWO SWITCHES FOR GENERATOR
Outstanding Inspections
Permit Status: Withdrwn
Permit Number: T00EL01323
Permite Description: SERVICE:ADD PANEL/TWO SWITCHES FOR GENERATOR
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| ELECTRIC - INTERMEDIATE | N/A | Not Inspected | ||
| 06/26/2000 | ELECTRIC - FINAL | N/A | Correction Required | ADDTL COMMS - 1. PLEASE USE NUT AND BOLT CONNECTION FOR GROUND BAR AT TRANSFER SWITCH 2. B.S. PANEL MAIN BREAKER REQUIRES A MIN BREAKER RETAINER 3. CIRCUIT #4 CONNECTOR (EMT) LOOSE 4. IMPROPER MINIMUM CLEARANCE IN FRONT OF PANEL BOARDS PLEASE MADE CORRECTIONS AND RECALL |