Permit: T00EL01280
Permit Details
Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
2310 S SAWTELLE AV
Address NEW:
2310 S SAWTELLE AV
Apply Date:
05/22/2000
Applicant:
DISCHER WILFRED A
Description:
UPGRADE:ELECTRIC 60AMP TO 100AMP
Outstanding Inspections
Permit Status: Expired
Permit Number: T00EL01280
Permite Description: UPGRADE:ELECTRIC 60AMP TO 100AMP
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/02/2000 | ELECTRIC - SERVICE UPGRADE | N/A | Correction Required | ADDTL COMMS - 1. SERVICE MOUNTED TOO HIGH 2. DONT RE-USE EXISING EQUIP. SINCE ITS NOT APPROVED AS WEATHER PROOF 3. A C-11 LIC. CONTRACTOR IS REQUIRED AT THIS TIME TO FINISH THIS JOB (TOO MANY MISTAKES 4. INCORRECT WIRE SIZING 5. IMPROPER BREAKERS 6. USE CONNECTOR AT BACK OF PANEL K.O. BUSHING IS NOT AN APPROPRIATE FITTING FOR THIS USE 7. WATER AND GAS BOND TO BE ABOVE GRADE HAVE THE C-11 LIC. CONTRACTOR CALL ME AT 909-5147 PRIOR TO NEXT INSPECTION |
| 06/02/2000 | ELECTRIC - FINAL | N/A | Correction Required | ADDTL COMMS - 1. SERVICE MOUNTED TOO HIGH 2. DONT RE-USE EXISTING EQUIP. SINCE ITS NOT APPROVED AS WEATHER PROOF 3. A C-11 LIC CONTRACTOR IS REQUIRED AT THIS TIME TO FINISH THIS JOB (TOO MANY MISTAKES) 4. INCORRECT WIRE SIZING 5. IMPROPER BREAKERS 6. USE CONNETCTOR AT BACK OF PANEL 7. WATER AND GAS BOND TO BE ABOVE GRADE HAVE THE C-11 LIC. CONTRACTOR CALL ME AT 909-5147 PRIOR TO NEXT INSPECTION |