Permit: T00EL01143
Permit Details
Apply Date:
05/04/2000
Applicant:
DOMINGUEZ PORFIRIO A JR
Description:
UPGRADE:ELECTRIC 60AMP TO 100AMP
Outstanding Inspections
Permit Status: Expired
Permit Number: T00EL01143
Permite Description: UPGRADE:ELECTRIC 60AMP TO 100AMP
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/11/2000 | ELECTRIC - FINAL | N/A | Correction Required | ADDTL COMMS - 1. NEED GAS BOND 2. NEED TO SEE WATER BOND TO SERVICE 3. NEED PERMANENT METAL ENGRAVED AOR RAISED ADDRESS TAG 4. INSTALL BUSHINGS TOP OF CONDUITS |