Permit: T00EL01109
Permit Details
Apply Date:
05/01/2000
Applicant:
PORTER THOMAS
Description:
RECONNECT:ELECTRIC-DUPLEX
Outstanding Inspections
Permit Status: Expired
Permit Number: T00EL01109
Permite Description: RECONNECT:ELECTRIC-DUPLEX
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/02/2000 | ELECTRIC - FINAL | N/A | Correction Required | ADDTL COMMS - 1. REWIRED WITHOUT INSPECTION OPEN AREAS FOR INSPECTION 2. SMOKE DETECTOR MISSING (HALLWAY) 3. OPEN LAMP FIXTURES NOT ALLOWED IN CLOSETS 4. NEW METAL J-BOX NOT GROUNDED 5. FIXTURES MISSING 6. ROMEX CONNECTORS BACKWARDS AT EAST UNIT CEILING J-BOX 7. NEED COOLERS PER MIN. HOUSING 8. REMOVE LOCKS SO I CAN INSPECT BACKYARD WITHOUT RIPPING LIKE I DID CLIMBING FRONT FENCE 9. APPEARS TO BE NEW PLUMBING GET APPROPRIATE PLUMBING PERMITS. |