Permit: T00EL00367
Permit Details
Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
1056 S BRIGHTON AV
Address NEW:
1056 S BRIGHTON AV
Apply Date:
02/10/2000
Applicant:
RUIZ OLIVIA
Description:
UPGRADE:ELECTRIC 30 AMP TO 100 AMP
Outstanding Inspections
Permit Status: Expired
Permit Number: T00EL00367
Permite Description: UPGRADE:ELECTRIC 30 AMP TO 100 AMP
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/14/2000 | ELECTRIC - SERVICE UPGRADE | N/A | Correction Required | ADDTL COMMS - 1. REMOVE BUSH IN FRONT OF SERVICE 2. INSTALL GROUND WIRE IN WEDGE OF ROD CLAMP 3. USE 1/4 LAG BOTH (IE. 1/4 HARDWARE) AT PIPE STRAP RECALL INSPECTION. |
| 07/07/2000 | ELECTRIC - FINAL | N/A | Denied | 1. NEED PROPER WORKING CLEARANCE IN FRONT OF SERVICE EQUIPMENT 3FT OUT X 30" WIDE 2. MUST OST PERMIT AND ALL PREVIOUS INSPECTION RESULTS 3. NEED TO ENTER TO CHECK TERMINATION 4. ALL 20 AMP CIRCUITS IN HOUSE? 5. NEED SEAL. LOCK NUT AT ENTRY INTO PANELBOARD (TOP LEFT SIDE) 6. EXPOSE GROUND RODS AND LET ME KNOW WHERE WATER AND GAS BOND ARE AT 7. DRYER RECEPT MUST HAVE 'RAINT TIGHT" ENCLOSURE WHILE PLUGGED IN MAKE CORRECTION. A RE FEE MAY BE IMPOSED UPON NEXT INSPECTION |