Permit: T00EL00258
Permit Details
Status:
Closed
Type:
SINGLE FAMILY OTHER
Address:
751 W BUDMOORE TE #01
Address NEW:
751 W BUDMOORE TE #01
Apply Date:
01/31/2000
Applicant:
ROSE WENDELLE A
Description:
RECONNECT:ELECTRIC RESIDENCE
Outstanding Inspections
Permit Status: Closed
Permit Number: T00EL00258
Permite Description: RECONNECT:ELECTRIC RESIDENCE
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/02/2000 | ELECTRIC - RECONNECT | N/A | Correction Required | ADDTL COMMS - 1. INSTALL SMOKE DETECTORS IN ALL BEDROOMS 2. MISSING SW BEDROOM 3. GROUNDED AND UNGROUNDED OUTLET INSTALL CORRECT OUTLETS WHERE UNGROUNDED 4. OPEN J-BOXES IN WH ROOM AND STORAGE ROOM 5. IMPROPERLY RUN LIGHT FEED TO SE BEDROOM 6. OPEN WIRING IN PANEL THESE CIRCUIT APPEAR TO COME FROM A DIFFERENT METER BUT GO THUR UNIT #1 CORRECT THIS 7. SERVICE PANEL IS NOT MOUNTED TO STRUCTURE 8. INSTALL COVERS ON ALL RECEPTS AND SWS 9. KITCHEN EXHAUST FAN TO BE INSTALLED PROPERLY AND OUTLET BOX PROVIDED FOR ITS CONNECTION PROPERLY CONNECT HOOD TO VENT AND SEAL OPENING 10. INSTALL A WEATHERPROOF RECEPTACLE FOR COOLER ON ROOF HAVE A C-11 LICENSED ELECTRICAL CONTRACTOR GO THUR THIS UNIT AND APPROVE FOR SAFETY AND MAKE ABOVE CONNECTIONS, PROVIDE NAME AND COMPANY TO OFFICE AT 791-5550 EXT 136 |