Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
3117 E 26TH ST
Address NEW:
3117 E 26TH ST
Apply Date:
01/12/2000
Applicant:
HOUSING & URBAN DEVELOPMENT SECR
Description:
RECONNECT:ELECTRIC:SFR

Outstanding Inspections

Permit Status: Expired
Permit Number: T00EL00096
Permite Description: RECONNECT:ELECTRIC:SFR
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
01/14/2000 ELECTRIC - RECONNECT N/A Correction Required ADDTL COMMS - 1. GROUNDING RECEPTACLES ARE NOT ALLOWED ON UNGROUNDED CIRCUIT UNLESS GFCI PROTECTED 2. INSTALL SMOKE DETECTOR IN HALLWAY 3. OPEN LAMP FIXTURE NOT ALLOWED ABOVE CLOSET SHELF 4. UPGRADE SERVICE TO 200 AMPS OR CALCULATE LOAD AND UPGRADE 5. PHYSICALLY PROTECT ALL EXPOSED WIRING.