Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address NEW:
1814 E BLACKLIDGE DR
Apply Date:
01/11/2000
Applicant:
JIM GLOVER ELECTRIC
Description:
UPGRADE:ELECTRIC
Contractors:
  • JIM GLOVER ELECTRIC

Outstanding Inspections

Permit Status: Expired
Permit Number: T00EL00082
Permite Description: UPGRADE:ELECTRIC
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
01/20/2000 ELECTRIC - SERVICE UPGRADE N/A Correction Required ADDTL COMMS - 1. CONDUCTOR IN RISER MUST BE LISTED SUNLIGHT RESISTANT 2. USE ONLY BREAKERS SPECIFIED IN PANEL BOARD LISTING 3. NEED GAS BOND? 4. OBTAIN PERMIT FOR TRAILER, INSTALL PER CODE AND CALL INSPECTION.