Permit Details

Status:
C of o
Type:
COMMERCIAL ADDITION
Address:
6255 E GRANT RD
Address NEW:
6255 E GRANT RD
Apply Date:
10/26/2000
Applicant:
METRO PERMIT EXPRESS, INC
Description:
ADDITION:FOOD COURT
Architects:
  • LEE, JERRY QUINN

Permit Reviews

Permit Number - T00CM05281
Permit Status: C of o
Permit Description: ADDITION:FOOD COURT
Start Date Submittal Complete Date Status  
03/28/2002 REVISION 05/23/2002 COMPLETED Review Details
05/02/2001 SITE 05/02/2001 COMPLETED Review Details
05/03/2001 RESUBMITTAL 05/03/2001 COMPLETED Review Details
10/26/2000 3RD PARTY COMMERCIAL TI 05/03/2001 COMPLETED Review Details

Completed Inspections

Permit Status: C of o
Permit Number: T00CM05281
Permit Description: ADDITION:FOOD COURT
Total Completed Inspections - 20
Date Description Inspector Results Comments
04/07/2002 EXCAVATION/LAYOUT REBAR & ZON AQUIROZ Approved IVRS - Inspection 0000*
04/17/2002 REINFORCED MASONRY PRE-GROUT AQUIROZ Approved IVRS - Inspection 0000*
04/22/2002 BUILDING PRE-SLAB AQUIROZ Approved IVRS - Inspection 0000*
04/29/2002 ROOF NAILING AQUIROZ Approved IVRS - Inspection 0000*
05/13/2002 PLUMBING - FINAL TRINIVJR Approved IVRS - Inspection 0000*1.) FINAL CONNECTION TO A.C. UNIT IS OK 2.) P.O.C. OF 1/2" C.W. SUPPLY TO COOLERS IS OK.
05/13/2002 ELECTRIC - INTERMEDIATE MCAPISTR Approved IVRS - Inspection 0000*PLEASE REVISE PLANS TO REFLECT MISSIONS AND ADDITIONS OF ELECTRICAL DEVICES ETC. SUBMIT FOR C.O..T. APPROVAL. ANY AND ALL REVISIONS MUST BEAR THE SEAL OF THE ENGINEER OF RECORD.
05/15/2002 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection 0000*
05/15/2002 ELECTRIC - FINAL DSANTACR Approved IVRS - Inspection 0000*1.) SUPPORT CONDUIT WITHIN 3' OF EACH J-BOX OR TERMINATION PER NEC. 2.) HOME RUNS UTILIZING EXISTING 8 X 8 J-BOX MTD. BY LOAD CENTERS CANNOT HAVE SPLICES FROM DIFFERENT SYSTEMS WITHOUT A DIVIDER . PER 300 NEC.
05/15/2002 ELECTRIC - FINAL DSANTACR Approved IVRS - Inspection 0245*
05/20/2002 SIGN - FINAL JYBARRA Approved IVRS - Inspection 0000*
05/20/2002 FIRE - FINAL LTHOMAS Approved
05/20/2002 FIRE SPKLR - FINAL LTHOMAS Approved
05/20/2002 FIRE SPKLR - OH PIPING & HYDRO LTHOMAS Approved
06/18/2002 BUILDING - FINAL RSUBA Approved IVRS - Inspection 0000*APPROVED SUBJECT TO ACCEPT OF SPECIAL INSPECTION REPORTS.
06/20/2002 ELECTRIC - UFER RSUBA Approved
06/20/2002 SHEET ROCK NAILING RSUBA Approved
06/20/2002 U VALUE FOR WINDOW RSUBA Approved
06/20/2002 FRAMING RSUBA Approved
06/20/2002 STEM WALL/RETAINING WALL RSUBA Approved
07/11/2002 PERMIT FINALED JYBARRA Approved