Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T00CM03803
Permit Details
Apply Date:
08/01/2000
Applicant:
ADAMS ANDA SSOCIATES
Description:
DISPENSER:UPGRADE
Permit Reviews
Permit Number - T00CM03803
Permit Status: Expired
Permit Description: DISPENSER:UPGRADE
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
08/01/2000 | COMMERCIAL TI | 03/05/2001 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T00CM03803
Permit Status: Expired
Permit Description: DISPENSER:UPGRADE
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
08/01/2000 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T00CM03803
Permite Description: DISPENSER:UPGRADE
Total Outstanding Inspections - 2
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/04/2001 | ELECTRIC - INTERMEDIATE | N/A | Denied | IVRS - Inspection 0245*1)NEED TO HAVE DISPENSER LISTED BY AN OSHA APPROVED TEST LAB EG. U.C, C.S.A. ETC.2)SEAL OFF TO BE WITHIN 18" OF ENCLOSURE AT DISPENSER.WATCH SEAL OFF AT CHANGE IN CLASIFICATIONS. |
08/09/2001 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0999*NEED LISTING OF DISPENSORS ETC. FM OR OTHER OSH APPROVED TEST LAB. |
Completed Inspections
Permit Status: Expired
Permit Number: T00CM03803
Permit Description: DISPENSER:UPGRADE
Total Completed Inspections - 2
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/04/2001 | BOILER FINAL | RLOHRMAN | Approved | IVRS - Inspection 0000* |
06/04/2001 | BOILER UNFIRED PRESSURE VESSEL | RLOHRMAN | Approved | IVRS - Inspection 0000* |