Permit: T00CM03325
Permit Details
Apply Date:
06/30/2000
Applicant:
FLUORESCO LIGHTING MAINTENANCE C
Description:
SERVICE:ELECTRIC
Contractors:
- FLUORESCO LIGHTING MAINTENANCE C
Permit Reviews
Permit Number - T00CM03325
Permit Status: Final
Permit Description: SERVICE:ELECTRIC
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 07/12/2000 | REVISION - RESUBMITTAL | 07/12/2000 | COMPLETED |
Completed Inspections
Permit Status: Final
Permit Number: T00CM03325
Permit Description: SERVICE:ELECTRIC
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2000 | ELECTRIC - FINAL | RMAJUTA | Approved | IVRS - Inspection 0999* PROVIDE VERIFICATION MANUFACTURED WIRING SYSTEM DOES NOT NEED ITS GROUND THAT ARMOR AND FITTING LISTED AND APPROVED FOR GROUNDING SEVERAL FIXTURES THRU OUT NOT SUPPORTED PER 99 NEC 410-16 BRACKETS NOT IN SEVERAL FIXTURES HAVE MISSING SEIMIC WIRES OLD RELOC WIRING TO BE REMOVED FROM CEILING NEW WIRING SYSTEM NOT TO BE LAYED ON TILE TO BE SUPPORTED FROM SEIMICS USED TO HANG FIXTURE REMOVE ANY OLD WIRING FROM PREVIOUS LIGHTING SYSTEM PLEASE PROVIDE A LISTING OF THIS MANUFACTURED WIRING SYSTEM TO ME FAX TO 791-4340 ATTENTION R MAJUTA HAVE APPROVED PLANS ON SITE |
| 01/22/2001 | PERMIT FINALED | RMAJUTA | Approved |