REMODEL:WH/LAV/KIT FAUCET/BASE BD HTR T99VL01713

Outstanding Inspections

Permit Status: Expired
Permit Number: T00CM00871
Permite Description: REMODEL:WH/LAV/KIT FAUCET/BASE BD HTR T99VL01713
Total Outstanding Inspections - 3
Last Inspection Date Description Inspector Results Comments
03/02/2000 ELECTRIC - FINAL N/A Correction Required ADDTL COMMS - DENIED - 1. ELECTRIC PANEL DOES NOT HAVE CIRCUITS LABELED. 2. DWV WASTE VENTS MUST EXTEND 6 ABOVE ROOF. 3. ABS AND PVC. DWV PIPE CANNOT BE INTERMIXED. 4. ABS, PVC, CPVC PLUMBING CANNOT BE USED ON EXTERIOR OF BUILDING UNPROTECTED. 5. WATER HEATER P & T VALVE DRAIN TUB MUST BE 3/4 MINIMUM. 6. WATER HEATER JUNCTION BOX IS NOT SECURE TO THE WALL AND MUST BE ELECTRICALLY BONDED. 7. W/C (TOILET) MUST HAVE 2 WASTE VENT.