Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T00CM00800
Permit Details
Apply Date:
02/17/2000
Applicant:
ROMAN CATHOLIC CHURCH DIOCESE OF
Description:
MODULAR CLASSROOMS (3) SITE APPR ON T99CM00903
Completed Inspections
Permit Status: Final
Permit Number: T00CM00800
Permit Description: MODULAR CLASSROOMS (3) SITE APPR ON T99CM00903
Total Completed Inspections - 2
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/23/2000 | ELECTRIC - UNDERGROUND | RMAJUTA | Approved | ADDTL COMMS - 1. 1-4 PVC CT CAN TO TEP TRANS OK COVER 2. 3-2 FEEDS FROM DISCONNECTS TO SENT 1ST UNIT OK TO COVER 3. HAVE PLANS ON SITE FOR FINAL 4. UFER TO GO TO NEUTRAL LUG THEN GUTTER TO NEUT IN CT CAN |
05/24/2000 | ELECTRIC - CABLE DROP | RMAJUTA | Approved | ADDTL COMMS - 1. 99 NEC 250-94 ALL PENETRATIONS THUR CONCENTRIC OR EXCENTRIC KOS REQUIRED TO HAVE GROUND BUSHINGS AT SERVICE EQUIPMENT (SOME PLASTIC 2. PLANS ON SITE ONLY APPROVED BY FIRE DEPT HAVE ONES APPROVED BY ELECT DEPT ON SITE NEED APPROVED OVEN TO FINAL |