Permit: T00CM00617
Permit Details
Status:
C of o
Type:
COMMERCIAL ALTERATION
Address:
2830 N SWAN RD #160
Address NEW:
2830 N SWAN RD #160
Apply Date:
02/10/2000
Applicant:
METRO PERMIT EXPRESS
Description:
TI:OFFICE
Contractors:
- KEMMERLY COMPANY , THE
Completed Inspections
Permit Status: C of o
Permit Number: T00CM00617
Permit Description: TI:OFFICE
Total Completed Inspections - 4
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/09/2000 | PLUMBING - ROUGH, SOIL | TRINIVJR | Approved | ADDTL COMMS - 1. SOIL WATER TEST OK 2. P.O.C. @ BLDG DRAIN OK 3. OK TO BACKFILL TRENCH |
| 03/29/2000 | PLUMBING - YARD WTR LINE/TEST | TRINIVJR | Approved | ADDTL COMMS - 1. WASTE AND VENT SYSTEM OK 2. OVERHEAD WATER DISTRIBUTION OK 3. YARD WATER LINE OK OK TO BACKFILL TRENCH. 4. MUST HAVE TEST AND CERTIFICATION ON BACKFLOW PREVENTERS BEFORE FINAL 5. NOTE: MUST HAVE SHUT OFF VALVE @ BLDG WATER SERVCIE |
| 03/30/2000 | PLUMBING - INTERMEDIATE | TRINIVJR | Approved | ADDTL COMMS - 1. WASTE AND VENT SYSTEM OK 2. OVERHEAD WATER DISTRIBUTION OK 3. YARD WATER LINE OK OK TO BACKFILL TRENCH 4. MUST HAVE TEST AND CERTIFICATION ON BACKFLOW PREVENTERS BEFORE FINAL 5. NOTE: MUST HAVE SHUT OFF VALVE @ BLDG WATER SERVICE |
| 05/18/2000 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | ADDTL COMMS - 1. INSTALL PLUG IN SECORNDARY DRAIN OUTLET ON AIR HANDLER 2. INSTALL TRAP ON PRIMARY CONDENSATE DRAIN LINE LEAVE OUT TILE IN THIS AREA WILL CHECK ON FINAL |