Parcel: 110120960

Inspection Status: Completed

Inspection History: COT - FOPR - Tent/Structure

Case Number - _E927A3790E0AA

Inspection Description - COT - FOPR - Tent/Structure

Inspection Status - Completed

Date Description Inspector Results Comments
10/28/2019 COT - FOPR - Tent/Structure Completed T19FO00934
TMC
2 TENTS SET UP 10.28.19
03/16/2019 COT - FOPR - Tent/Structure Completed T19FO00191

Safety Fair Be Safe Saturday

Event Date - 16 March, 2019

Contact - Greg Harris - 429-2743
08/24/2018 COT - FOPR - Tent/Structure Completed T18FO00699
TUCSON MEDICAL CENTER
SET-UP DATE: 08-16-18
(1) TENT
30 X 30
GTD SCHEDULED TO BE OUT TO INSPECT 08-24-18
03/17/2018 COT - FOPR - Tent/Structure Completed SAFETY FAIR
T18FO00212 - 10 TENTS
SETUP DATE 03/14/18

Missing pads at barrels

Repaired
12/14/2017 COT - FOPR - Tent/Structure Completed T17FO01023
1 TENT
SETUP DATE 12/13/17
TMC
10/30/2017 COT - FOPR - Tent/Structure Completed 2 TENTS
1 40 X 50 10/25/17
1 40 X 50 10/30/17
HALOWEEN PARTY 10/31/17
T17FO00905
Sent BC to site. Single Barrels
Contacted AZ PR for repairs
Me to site later in evening , no repairs made , no pads.
Event over, but they will be billed again/
03/17/2017 COT - FOPR - Tent/Structure Completed 0206

TMC LOT 11 - SAFETY FAIRE

21 TENTS

SET UP: 03-14-2017

CONTACT: GILBERT LUNA 327-6628
03/17/2016 COT - FOPR - Tent/Structure Completed JC 3/17/16 Did drive by and then research.. Spoke to Gilbert Luna (Director of Ops for AZ Party Rental) and asked him to
1) ensure all tents have NO SMOKING signs posted regardless of size.
2) provide illuminated exit signs and emergency egress lighting in largest 2 tents (20x50 and 30x60 )
3) Tent 30x60 have 3 exits
4) Tent 20x50 have 2 exits
5) Have minimum of 2 fire extinquishers in each of largest 2 tents
6) Have min of 1 fire extinguisher in each of 2 20x20 tents with sidewalls (used for storage)
7) Have fire extinquishers min of 75 feet of travel throughout for others.
03/20/2015 COT - FOPR - Tent/Structure Completed SET UP DATE 3-19 INSPECTION ON 3-20
05/02/2022 COT - FOPR - Tent/Structure Completed T22FO00265 TENT 05.02.22 THE EVENT GUY
03/23/2022 COT - FOPR - Tent/Structure Completed T22FO00271 TENT 03.26.22 THE EVENT GUY
01/13/2022 COT - FOPR - Tent/Structure Completed T22FO00038 3 TENTS 01.13.22 THE EVENT GUY

Tent Inspection completed.
10/28/2021 COT - FOPR - Tent/Structure Completed T21FO00744 TENT 10.28.21 2 TENTS FOR THE EVENT GUY
09/16/2021 COT - FOPR - Tent/Structure Completed T21FO00605 1 TENT 40' X 40' THE EVENT GUY
06/19/2021 COT - FOPR - Tent/Structure Completed SHADE STRUCTURE BY NORTH PARKING LOT
06/12/2021 COT - FOPR - Tent/Structure Completed T21FO00345 20x60 NE Maintenance Bldg (Equipment storage)
3 TENTS 6/12/21
03/21/2013 COT - FOPR - Tent/Structure Completed put plans in your box to assign

3/21/13 NOT READY FOR INSPECTION, NO FIRE EXTINGUISHERS OR EXIT SIGNS
04/24/2012 COT - FOPR - Tent/Structure Completed Tent TMC // Tent went up and came down on Sat. Paperwork stated final due on 4/24/2012. I went by and found nothing, I called the tent Co. and they stated the above , and that she "hit the wrong button" //Ma 30 spent 1/2 hour looking on campus for the tent that had already been removed. Carl shultz was notified of all of the above. // No further action // closed.
10/02/2021 COT - FOPR - Tent/Structure Completed T21FO00744 TENT 10.28.21 2 TENTS FOR THE EVENT GUY