09/06/2019 | COT - Fire - Complaint | Completed | IROL SPI 5.24.19 KAZAL Monterey Village 6130 Vacant Ques: Sprinkler heads appear free of corrosion, foreign material, paint or damage, no signs of leakage and heads/deflectors installed in proper orientation (5.2.1.1.) Technician Response: 5 painted 1/2" chrome 155° SR pendents w/ chrome 3 in NW corner by stair stepper 2 by so fit above weight rac Ques: # of replacement sprinkler heads per # installed in head box comply: 6 per 1-300: 12 per 301 to 1,000: 24 per 1,000 (5.4.1.5) Technician Response: 6 1/2" chrome 155° Sr pendents missing from head box Ques: Sprinkler head wrench for each type head provided in head box (5.4.1.6) Technician Response: Missing head wrench Cleared pr Kazal |
|
01/05/2018 | COT - Fire - Complaint | Completed | 08-03-2017 Cathy Welsh Monterey Village 6130 E Speedway blvd. Tucson, AZ 85712 520- 977-7790 cwelch@4-dproperties.com Subject: NOTICE OF VIOLATION As required by the 2012 Tucson Fire Code, your Fire Protection System must be inspected/tested annually and quarterly. A written report shall be forwarded to the Tucson Fire Department (TFD). TFD received a report (fire sprinklers) for your business from Kazal Fire Protection. During that inspection, deficiencies were noted on the report, which are violations of the requirements in Section 901.6 of the 2012 Tucson Fire Code. If the deficiencies have not already been corrected; please contact a qualified Fire Protection Company as soon as possible to make these corrections. Due to Life/Safety concerns, these violations must be corrected, and this office notified within 14 days. (August 17th 2017) Jennifer Peel-Davis Fire Code Inspector Tucson Fire Department 520-837-7033 Jennifer.peel-davis@tucsonaz.gov IROL SPI 07.18.17 08-03-2017 JMPD |
|
09/02/2020 | COT - Fire - Complaint | Completed | Told more tents added, may impede on FDC access. Found pop-up blocking view to |