Parcel: 12710084B


Addresses:

6130 E SPEEDWAY BL


Inspection Status: Completed

Inspection History: COT - Fire - Complaint

Case Number - _E42618098E922

Inspection Description - COT - Fire - Complaint

Inspection Status - Completed

Date Description Inspector Results Comments
09/06/2019 COT - Fire - Complaint Completed IROL SPI 5.24.19 KAZAL


Monterey Village 6130 Vacant
Ques: Sprinkler heads appear free of corrosion, foreign material, paint or damage, no signs of leakage and
heads/deflectors installed in proper orientation (5.2.1.1.)
Technician Response: 5 painted 1/2" chrome 155° SR pendents w/ chrome
3 in NW corner by stair stepper 2 by so fit above weight rac
Ques: # of replacement sprinkler heads per # installed in head box comply: 6 per 1-300: 12 per 301 to 1,000: 24 per
1,000 (5.4.1.5)
Technician Response: 6 1/2" chrome 155° Sr pendents missing from head box
Ques: Sprinkler head wrench for each type head provided in head box (5.4.1.6)
Technician Response: Missing head wrench

Cleared pr Kazal
01/05/2018 COT - Fire - Complaint Completed 08-03-2017

Cathy Welsh
Monterey Village
6130 E Speedway blvd.
Tucson, AZ 85712
520- 977-7790
cwelch@4-dproperties.com

Subject: NOTICE OF VIOLATION


As required by the 2012 Tucson Fire Code, your Fire Protection System must be inspected/tested annually and quarterly. A written report shall be forwarded to the Tucson Fire Department (TFD). TFD received a report (fire sprinklers) for your business from Kazal Fire Protection. During that inspection, deficiencies were noted on the report, which are violations of the requirements in Section 901.6 of the 2012 Tucson Fire Code. If the deficiencies have not already been corrected; please contact a qualified Fire Protection Company as soon as possible to make these corrections. Due to Life/Safety concerns, these violations must be corrected, and this office notified within 14 days. (August 17th 2017)


Jennifer Peel-Davis
Fire Code Inspector
Tucson Fire Department
520-837-7033
Jennifer.peel-davis@tucsonaz.gov
IROL SPI 07.18.17

08-03-2017 JMPD
09/02/2020 COT - Fire - Complaint Completed Told more tents added, may impede on FDC access.

Found pop-up blocking view to