Inspection History Details
Inspection Status: Completed
Inspection History: COT - Fire - Complaint
Case Number - _80D759E9E90DB
Inspection Description - COT - Fire - Complaint
Inspection Status - Completed
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/15/2023 | COT - Fire - Complaint | Completed | KHI, 06.09.22, UNITED FIRE No exhaust fan control for main kitchen Ansul Systems. Micro switches need installed and connected to exhaust fans. Exhaust fans are required to stay running apon system activation |
|
09/22/2015 | COT - Fire - Complaint | Completed | JCC - HYDRO DUE x 3 BC 7/6/15 Inspector Spangle stated managers are in process of buying new bottles. Ck back in 2 weeks. 349-4268 9/16/15 Done [bought new bottles] - waiting for paperwork. Ed Burk- United Fire /// Done 8/25/15 /// Closed. |